Example 1
- Volume: 50 m³
- Heat demand: 40 W/m³
Heating power: 2000 W
That is about 2.00 kW
This is a straightforward example of moving from volume to an approximate heating power value.
Type room volume in m³ and a W/m³ figure. The calculator multiplies them to watts and shows kilowatts. A 50 m³ room at 40 W/m³ is 2000 W, about 2.00 kW. An 84 m³ living room at 35 W/m³ is 2940 W. A 27.3 m³ bedroom at 45 W/m³ is 1228.5 W, about 1.23 kW.
This calculator gives a fast, approximate heating power result based on room volume and an assumed W/m³ demand value. It is useful for first comparisons, but it does not replace a full heat-loss calculation. Related: room volume, insulation requirement.
Room volume (m³), Heat demand (W/m³), Building standard (auto W/m³) and Room type. The result shows up here.
The heating calculator sketches power from volume. The formula is m³ times W/m³, and kW is watts divided by 1000. Room type and window area refine the result only when you fill them. Building standard can supply the figure when you leave W/m³ empty.
A 50 m³ room at 40 W/m³ is 2000 W, two kilowatts for an ordinary living room. A taller 84 m³ salon at 35 W/m³, a warmer standard, is 2940 W. A small 27.3 m³ bedroom at 45 W/m³ is 1228.5 W. Those three volumes come from the volume card: 5×4×2.5, 6×5×2.8, and 3.5×3×2.6 m.
Type room volume and heat demand in W/m³, or pick a building standard. Leave room type and windows empty when the plain product is enough. A comma in 27.3 works the same as 27,3.
The 50 m³ volume lives on the room volume calculator. Insulation for 120 m² at 60×120 cm and 8% is 181 boards and R about 4.17, another calculator. Paint does not turn into watts.
This is a sketch, not a design heat loss. An older house sits nearer 45-50 W/m³, a newer one nearer 30-35. Empty windows add nothing. Type 50 and 40, click Calculate, and match 2000 W and 2.00 kW.
Then 84 and 35: 2940 W. 27.3 and 45: 1228.5 W, the third card.
Volume times the W/m³ figure. A 50 m³ room at 40 W/m³ is 2000 W, about 2.00 kW.
Heating power: 2000 W
That is about 2.00 kW
This is a straightforward example of moving from volume to an approximate heating power value.
Heating power: 2940 W
That is about 2.94 kW
A lower W/m³ demand can offset a larger room volume if the building standard is better.
Heating power: 1228.5 W
That is about 1.23 kW
A smaller room does not always mean very low heating power if the assumed demand value is higher.
2000 W, about 2.00 kW. That is the first card example.
2940 W, about 2.94 kW. A 6×5×2.8 m living room from volume.
1228.5 W, about 1.23 kW. A small bedroom, a higher figure.
From room volume: 5×4×2.5 m = 50. Walls and paint are other cards.
No. Windows and room type enter only when you fill them.
A sketch of 40 for an ordinary room. An older building sits nearer 45-50, a newer one 30-35. Standard can fill the number for you.
It is the product of two fields. Heat loss, bridges, and ventilation stay off the calculator.
Not on this page. Insulation counts boards and R. Here it stays W = m³ × W/m³.
Yes. 27.3 and 27,3 are the same volume. At 45 W/m³ you get 1228.5 W.
4000 W, which is 4.00 kW. The formula is linear: volume times the W/m³ sketch.
Volume and waste come from the sizes you type. Below are volume and NIST SI units.
Page updated in 2026.